国产一级淫片一区二区三区在线|亚洲国产一区二区三区视频在线|日韩精品国产中文字幕一区二区|日韩中文字幕在线观看国产

您好,歡迎來到濟南通宇恒成自動化工程有限公司網(wǎng)站!

服務(wù)熱線

當(dāng)前位置: 首頁- 新聞中心 > 客戶見證
常見問題
新聞中心

電氣成套所存在的問題干貨分享

發(fā)布時間:2022-05-30 來源:http://www.ywf-lanzhou.com/ 瀏覽量:

接地排截面積小于進線截面積
The sectional area of grounding bar is smaller than that of incoming line
接地排過多的打孔更減小截面積
Too many holes are punched in the grounding bar to reduce the cross-sectional area
接地并線,增加接地阻抗
Grounding and paralleling to increase grounding impedance
柜體安裝底板,框架均未接地
The bottom plate of the cabinet is installed, and the frame is not grounded
未采取分層接地的措施
Layered grounding measures are not taken
通訊電纜與強電電纜平行敷設(shè)
Communication cable and strong current cable shall be laid in parallel
通訊線屏蔽層強制接地在絕緣部位
The shielding layer of communication line is forcibly grounded at the insulating part
DP總線未正確的固定與屏蔽,CU320模塊的用于固定與屏蔽電纜線的附件缺失。
DP bus is not properly fixed and shielded, and accessories for fixing and shielding cable of cu320 module are missing.
編碼器線,裝置通訊線隨意懸空,未作固定,編碼器線亦未作屏蔽。
The encoder line and the device communication line are suspended at will, not fixed, and the encoder line is not shielded.
CU320控制單元及接口模塊均未做接地處理。
Cu320 control unit and interface module are not grounded.
電氣成套傳動裝置未安裝屏蔽附件,安裝位置偏低,且被線槽阻擋,導(dǎo)致冷卻風(fēng)道被阻擋,裝置進出線不合理。
The complete set of electrical transmission device is not installed with shielding accessories. The installation position is low and blocked by trunking, resulting in blocked cooling air duct and unreasonable incoming and outgoing lines of the device.
柜體進線位置設(shè)計不合理。
The design of cabinet incoming line position is unreasonable.
主開關(guān)出線采用并線,接觸電阻增大,易發(fā)熱。
The outgoing line of the main switch adopts parallel line, which increases the contact resistance and is easy to heat.
母排設(shè)計結(jié)構(gòu)不合理,進出線混亂,大截面線存在繞圈布線的現(xiàn)象。
The busbar design structure is unreasonable, the incoming and outgoing lines are disordered, and the large section line has the phenomenon of circular wiring.
母排與底板,母排與母排,各相電線之間的絕緣間距不夠。
The insulation spacing between busbar and baseboard, busbar and busbar, and wires of each phase is insufficient.
電氣成套
母排截面積小于進線截面積,并且大量打孔,導(dǎo)致有效截面積進一步減小,從而導(dǎo)致載流量減小。
The sectional area of busbar is smaller than that of incoming line, and a large number of holes are punched, which further reduces the effective sectional area and leads to the reduction of ampacity.
母排各路出線未作限流保護,易由小線路短路導(dǎo)致整個線路短路引發(fā)線路起火等重大事故。
The outgoing lines of the busbar are not provided with current limiting protection, which is easy to cause the short circuit of the whole line due to the short circuit of the small line and cause major accidents such as line fire.
線纜顏色使用不規(guī)范。
The cable color is not standardized.
強電線路與信號線捆扎在一起行線
Strong current lines and signal lines shall be bundled together for running
通訊線屏蔽層懸空,儀表未有效接地
The shielding layer of communication line is suspended, and the instrument is not effectively grounded
電纜跨門安裝結(jié)構(gòu)不合理,電線易斷
The cable cross door installation structure is unreasonable, and the wire is easy to break
柜門安裝布線亦應(yīng)使用線槽,并分類行線
Wiring for cabinet door installation shall also use trunking and classified wiring
溫控模塊加熱控制線未用雙絞屏蔽線
No twisted pair shielded wire is used for the heating control wire of the temperature control module
電氣成套采用鋁制導(dǎo)軌,并且無接地端子
Aluminum guide rail is used in the electrical package, and there is no grounding terminal
通訊線的接地方式不正確,接地效果不明顯
The grounding mode of communication line is incorrect, and the grounding effect is not obvious
熱電阻輸入信號線未采用屏蔽電纜,未采用測量精度較高的3線制或4線制接法
The thermal resistance input signal line does not use shielded cable, and the 3-wire system or 4-wire system connection method with high measurement accuracy is not used
強電端子正在信號端子的下方,間距很小
The strong current terminal is under the signal terminal with a small spacing
強電線與信號線平行敷設(shè)在同一線槽內(nèi)
Strong wire and signal wire are laid in the same slot in parallel
濾波器可以不用
Filter may not be used
如需使用濾波器應(yīng)根據(jù)負(fù)載的實際大小選用濾波器的規(guī)格,這里20A明顯大多了,不起作用
If you need to use a filter, you should select the filter specification according to the actual size of the load. Here, 20A is obviously too much and does not work
電氣成套接地端子被用作固定端子
The complete electrical grounding terminal is used as a fixed terminal
雙空開為何只有一相出線
Why is there only one phase outgoing line for double air switches
電氣成套所存在的問題干貨分享內(nèi)容就到這里了,還有很多事項問題需要大家在實際應(yīng)用中多多觀察記錄預(yù)防,您可以來我們網(wǎng)站www.ywf-lanzhou.com和客服人員聯(lián)系分享交流。
That's all for dry goods sharing. There are still many problems that need to be observed, recorded and prevented in practical application. You can visit our website at www.tongyuhengcheng COM and customer service personnel.
首頁首頁 產(chǎn)品產(chǎn)品 電話電話 置頂置頂