使用電氣設(shè)備或在電源周圍工作時(shí),必須使用個(gè)體防護(hù)用品。如戴絕緣手套,穿保護(hù)性或絕緣性的圍裙及鞋。此外
電氣成套設(shè)備的零部件使用要怎么使用呢?
Personal protective equipment must be used when using electrical equipment or working around the power supply. For example, wear insulating gloves, protective or insulating aprons and shoes. In addition, how to use the parts of the complete electrical equipment safely?
配電柜柜內(nèi)的電子元件的布置要盡量遠(yuǎn)離主回路、開關(guān)電源及變壓器,不得直接放置或靠近柜內(nèi)其他發(fā)熱元件的對(duì)流方向。
The electronic components in the distribution cabinet shall be arranged as far away from the main circuit, switching power supply and transformer as possible, and shall not be placed directly or close to the convection direction of other heating components in the cabinet.
主令操縱電器元件及整定電器元件的布置應(yīng)避免由于偶然觸及其手柄、按鈕而誤動(dòng)作或動(dòng)作值變動(dòng)的可能性,整定裝置一般在整定完成后應(yīng)以雙螺母鎖緊并用紅漆漆封,以免移動(dòng)。
The arrangement of the master control electrical components and the setting electrical components shall avoid the possibility of misoperation or action value change due to accidental touch of its handle and button. Generally, the setting device shall be locked with double nuts and sealed with red paint after setting to avoid movement.
系統(tǒng)或不同工作電壓電路的熔斷器應(yīng)分開布置。
The fuses of the system or circuits with different working voltages shall be arranged separately.
熔斷器、使用中易于損壞、偶爾需要調(diào)整及復(fù)位的零件,應(yīng)不經(jīng)拆卸其他部件便可以接近,以便于更換及調(diào)整。
Fuses and parts that are easily damaged in use and occasionally need to be adjusted and reset shall be accessible without disassembling other parts for easy replacement and adjustment.
熔斷器安裝位置及相互間距離應(yīng)便于熔體的更換。
The installation position and distance between fuses shall facilitate the replacement of the melt.
不同電壓等級(jí)的熔斷器要分開布置,不能交錯(cuò)混合排列。
Fuses of different voltage levels shall be arranged separately and cannot be staggered and mixed.
有熔斷指示器的熔斷器,其指示器應(yīng)裝在便于觀察的一側(cè)。
For fuse with fuse indicator, the indicator shall be installed on the side convenient for observation.
瓷質(zhì)熔斷器在金屬底板上安裝時(shí),其底座應(yīng)墊軟絕緣襯墊。
When the porcelain fuse is installed on the metal base plate, its base shall be padded with soft insulation gasket.
低壓斷路器與熔斷器配合使用時(shí),熔斷器應(yīng)安裝在電源側(cè)。
When low-voltage circuit breaker and fuse are used together, the fuse shall be installed on the power supply side.
強(qiáng)弱電端子應(yīng)分開布置;當(dāng)有困難時(shí),應(yīng)有明顯標(biāo)志并設(shè)空端子隔開或設(shè)加強(qiáng)絕緣的隔板。
Strong and weak current terminals shall be arranged separately; In case of difficulties, clear signs shall be provided and empty terminals shall be set for separation or partition with strengthened insulation shall be set.
In addition, the corresponding terminals shall have serial numbers, and the terminal strip shall be convenient for replacement and wiring; The height from the ground should be greater than 350 mm. Come to our website for more relevant content http://www.ywf-lanzhou.com Ask!